Medium Voltage Distribution
Catalogue | 2013

RL-Series
Load Break Switch/Sectionaliser
with ADVC controller

Page 12

10 AMTED300052EN

RL-Series WSOS version 5

Measurement screens
b Three-phase, earth and sequence current
b Phase voltages:
v Phase to phase,
v Phase to earth, and
v Sequence voltages.
b Phase live/dead indication
b Apparent, reactive & real power:
v Total, and
v Per phase.
b Power factor
b Signed or unsigned power
b Frequency
b Power quality toolkit:
v Waveform capture
v Harmonics.

Interface confi guration
b Status lamps:
v Logic function to indicate; and
v Separate true/false state colour confi guration.
b Quick action keys:
v Customise actions assigned to each key
v Custom logic functions for lamp indication, and
v Separate true/false colour confi guration.
b Print labels to insert into Operator Interface.

Example of panel confi guration tool

P
E

55
51

0

Page 13

11AMTED300052EN

RL-Series Advanced detection /
Sectionalising features

Fault detection

Phase fault detection
Phase fault detection monitors all three phases and makes event log entries
on through-fault detection.

b Phase faults setting range: 10 - 1260 A
b Setting resolution: 1 A
b Detection time range: 0.01 - 100 s
b Time resolution: 0.01 s

Earth fault detection
Earth fault detection monitors earth faults and makes event log entries on through-
fault detection.

b Earth faults setting range: 10 - 1260 A
b Setting resolution: 1 A
b Detection time range: 0.05 - 100 s
b Time resolution: 0.01 s

Sensitive Earth Fault (SEF)
SEF causes a fault to fl ag when the earth current rises above a set level for longer
than the set time.

b SEF current range: 4 - 20 A
b SEF operating time range: 0.1 - 999 s
b SEF current setting resolution: 1 A
b SEF operating time resolution: 0.1 s

Defi nite time protection
Defi nite time works by fl agging a fault at a fi xed time after pick-up.

b Setting current range: 10 - 1260 A
b Defi nite time resolution: 0.01 s
b Defi nite time range: 0.01 - 100 s
b Setting current resolution: 1 A

Inrush restraint
Inrush restraint raises the phase and earth threshold currents for a short period of
time to allow for short duration inrush currents when closing onto a load.

b Multiplier range: 1 - 30
b Multiplier resolution: 0.1
b Time range: 0.05 - 30 s
b Time resolution: 0.05 s

Sequence components
Negative, positive and zero phase sequence currents and voltages can be
monitored and logged.
In addition, the negative phase sequence current detection can be used for detection
of low-level phase-to-phase faults in the presence of high level three-phase loads.

b Setting current range: 10 - 1260 A

Page 24

AMTED300052EN 03-2013

As standards, specifi cations and designs change from time
to time, please ask for confi rmation of the information given
in this publication.

Design: Schneider Electric Industries SAS
Photos: Schneider Electric Industries SAS
Printed: Altavia St-Etienne - Made in France

335, rue Joseph Monier
CS 30323
F - 92506 Rueil Malmaison Cedex (France)
Tel.: +33 (0)1 41 29 70 00
RCS Nanterre 954 503 439
Capital social 896 313 776 €
www.schneider-electric.com

Schneider Electric Industries SAS

A
R

T
97

15
3

©
S

ch
ne

id
er

E
le

ct
ric

E
ne

rg
y

F
ra

nc
e

- A
ll

rig
ht

s
re

se
rv

ed

This document has been
printed on recycled paper

10-31-1247

Similer Documents